CE1 IEC (Première édition – ) (First edition – ) Courants de court-circuit dans les réseaux Short-circuit currents in three-phase. IEC Edition INTERNATIONAL. STANDARD. NORME. INTERNATIONALE. Short-circuit currents in three-phase a.c. systems –. Buy IEC SHORT-CIRCUIT CURRENTS IN THREE-PHASE A.C. SYSTEMS – PART 0: CALCULATION OF CURRENTS from SAI Global.

Author: Douran Kajisar
Country: Republic of Macedonia
Language: English (Spanish)
Genre: Science
Published (Last): 28 September 2010
Pages: 100
PDF File Size: 19.6 Mb
ePub File Size: 5.46 Mb
ISBN: 651-5-99879-163-6
Downloads: 32443
Price: Free* [*Free Regsitration Required]
Uploader: Zoloshura

It is not necessary for the product 1, Special methods to calculate i, with sufficient accuracy are given in 4.

Short Circuits in Power Systems: A Practical Guide to IEC 60909-0, 2nd Edition

Using this method, the currents in each line conductor are found by superposing the currents of the three symmetrical component systems: Transformer secondary short circuits.

Figure 1 gives schematically the general course of the short-circuit current in the case of a far-fiom- generator short 60099-0.

Example for the estimation of the contribution from the asynchronous motors in relation to the total short-circuit current Figure 16 can be used also for compound excited low-voltage generators with a minimum time delay tminnot greater than 0,1 s. The text of this standard is based on the following documents: In the case of high-voltage direct-current transmission systems, the capacitor banks and filters need special considerations, when calculating a.

The superposition method gives the short-circuit current related to the one load flow presupposed.

This does not exclude the use of 609009-0 methods, for example the superposition method, adjusted to particular circumstances, if they give at least the same precision. Examples f o r the calculation of short-circuit currentsi The committee has decided that the contents of this publication will remain unchanged until Short circuits may have one or more sources, as 60909-00 in figures 11, 12, and Xq 6090-90 reactance of a synchronous machine saturated valuedirect axis respectively quadrature axis xd Unsaturated synchronous reactance, relative value xd sat Saturated synchronous reactance, relative value, reciprocal of the saturated no-load short-circuit ratio Impedance, absolute respectively relative value Short-circuit impedance of a three-phase a.

  JERZY MYCIELSKI EKONOMETRIA PDF

Operational data and the load of consumers, tap- changer position of transformers, excitation of generators, and so on, are dispensable; additional calculations about all the different possible load flows at the moment of short circuit are superfluous. E” Subtransient voltage of a synchronous machine f Frequency 50 Hz or 60 Hz Ib Symmetrical short-circuit breaking current r.

60909–0 impedances of a three-phase a. Added to Your Shopping Cart. The generator impedance shall be transferred to the high-voltage side using the rated transformation ratio t. If not, they are subject to additional considerations.

IEC | IEC Webstore

Calculation of currents 1 General 1. As long as RIX remains smaller than 0,3 in all branches, it is not necessary to use the factor 1, The following types of unbalanced short circuits are treated in this standard: The initial line-to-earth short-circuit current Iil in figure 3d shall be calculated by: In the case of figure 4, for instance, to the LV side.

Read an Excerpt Excerpt 1: NOTE For some near-to-generator short circuits the value of id. For the short-circuit impedance of synchronous generators in the zero-sequence system, the following applies with KG from equation 1 8: This postulates that the electrical equipment has a balanced structure, for example in the case of transposed overhead lines. For increased accuracy, equations 79, 76and 77 can be used.

The value should be obtained from the manufacturer. O 1 marks the positive-sequence neutral reference. NOTE Equivalent circuits of the positive-sequence and the zero-sequence system are given in IECtable Iitem 4 to 7 for different cases of starpoint earthing. Radial Network When calculating unbalanced short-circuit 60990-0 in medium- or high-voltage systems and applying an equivalent voltage source at the short-circuit location, the zero-sequence capacitances of lines 60909–0 the zero-sequence shunt admittances are to be considered for uec.

  LAKATOS LEVENTE AKTUS PDF

The calculation of the minimum steady-state short-circuit current in the case of a near-to- generator short circuit, fed by one or’ several similar and parallel working generators with compound excitation, is made as follows: For these equivalent asynchronous motors, including their connection cables, the following may be used: Meshed Network They may be neglected. For this calculation method, an equivalent voltage source at the short-circuit location is introduced.

Definitions,principles and rules IEC 1: Short-circuit currents and short-circuit impedances may also be determined by system tests, by measurement on a network analyzer, or with a digital computer. Phasor diagram of a synchronous generator at rated conditions In the case of a near-to-generator short circuit, the short-circuit current can be considered as the sum of the following two components: The IEC shall not be held responsible for identifying any or all such patent rights.

It is only necessary to choose the branches which carry partial short-circuit currents at the nominal voltage corresponding to the short-circuit location and branches with transformers adjacent to the short-circuit location.

The impedances of the equipment in superimposed or subordinated networks are to be divided or multiplied by the square of the rated transformation ratio t. I education ci military ci I other The influence of various winding-temperatures on RGf is not considered.

The zero-sequence short-circuit impedance at the short-circuit location F is obtained according to figure 5c, if an a.

The estimation according to equation 28 is not allowed in the case of three-winding transformers.